• Mist Eliminators
  •     
  • Scrubbers
  •     
  • Heat Recovery Towers
  •     
  • P-5 Particulate Monitor
  •     
  • Trouble Shooting Service

  • Product Description:
  • The heat recovery tower performs the following functions:
  • It quenches the gas (if it is not already water saturated)
  • It recovers heat from the inlet gas
  • It condenses out excess moisture
  • The gas discharges to the atmosphere at a much lower temperature than before
  • As a result of the condensation of moisture in the tower, additional particulate is “scrubbed” from the gas

    Types Available:
    We use 4 different types of towers to recover heat.

    Type 1: Tray Towers
    These are the most thermally efficient and have the lowest capital cost. Their shortcomings are:

  • high pressure drop (~ 3" WG per tray)
  • more susceptible to fouling with solids

    Type 2: Grid-type Packed Towers
    These are less efficient and more expensive than tray towers.
    Their advantages over trays:

  • much lower pressure drop
  • much less susceptible to fouling

    Type 3: Spray Towers
    These are the least thermally efficient with a capital cost intermediate between trays and grid towers.
    Their advantages are:

  • low pressure drop
  • negligible likelihood of fouling

    Type 4: Packed (Random type) Towers
    Along with the tray tower, these are the most thermally efficient. Depending on whether plastic or metal packing can be used, they can also be the cheapest.

    Features of this type:

  • low pressure drop
  • most susceptible to fouling with solids

    Application:
    Most product dryer exhausts have to pass through some type of air pollution control equipment to remove solid particulate. The residual particulate content governs the selection of the type of heat recovery device.
    Some examples are:

  • Pulp/Paper Machine dryer: spray
  • Food Product Drying: low particulate – tray
    : high particulate - Grid
  • Mineral Product Drying: grid tower
  • Boiler off gas, scrubbed: low particulate - packed


    Our Scope of Supply:

  • Heat recovery towers complete with all internals and flanged nozzles
  • Installation and peripheral equipment is by others
  • Grid-type heat recovery tower with side entry and once-through sump Tray-type heat recovery tower with bottom entry and recirculation sump for mounting on top of a scrubber